c-pro 3 CHIL

c-pro 3 CHIL

Controllers for single- and dual-circuit chillers/heat pumps
c-pro 3 CHIL are controllers for running single- and dual-circuit air to water and water to water chillers/heat pumps, up to 3 compressors for each circuit.
It consists of:
- a main controller with a choice of a c-pro 3 nano CHIL (with a built-in user interface and touch keys) or a c-pro 3 micro CHIL (available with a built-in user interface or a blind version)
- a possible I/O expansion (c-pro 3 EXP micro+, available in blind version)
- a possible bipolar stepper electronic expansion valves driver for each circuit (EVDRIVE03, available with integrated user interface or in blind version)
- a possible remote user interface (Vgraph).
The system is able to manage “on-off” compressors; it is also able to manage both “on-off” and modulating fans, with single or independent condensation.
It can manage the pump down solenoid valve, “free cooling” and the “weekly programming” function.
c-pro 3 nano CHIL is designed to be installed on a panel with snap-in brackets, while c-pro 3 micro CHIL is fitted to a DIN rail in a control panel.
Technical sheet
Generate PDF

Advantages & Main Features

Flexibility, modularity and expandability.
Communication with a possible bipolar stepper electronic expansion valves driver (EVDRIVE03) for each circuit.
Management of “on-off” and modulating fans, with single or independent condensation.
Variety of communication ports (RS-485, CAN and USB) and supported communication protocols, to make the integration of the devices in systems easier.
Main controller available with integrated user interface or in blind version.
Management of 3 “on-off” compressors for each circuit.
Pump down valve management.
“Free cooling” management.
“Weekly programming” function.

Technical Features

Controllers for single- and dual-circuit chillers/heat pumps

c-pro 3 nano CHILc-pro 3 micro CHILc-pro 3 EXP micro+EVDRIVE03Vgraph
EPN2LXP1CHEPU2BXP1CHEPU2LXP1CHEPU2EXPEPD4BC3EPD4DF3EPV4GBR
Version
blind    
built-in LED (4+4 digits custom display)     
built-in LCD (128 x 64 pixel single colour LCD graphic display)     
Connections
Micro-Fit connectors   
removable spring terminal blocks     
removable screw terminal blocks
Power supply
12 VAC not isolated   
24 VAC/DC not isolated    
Communication ports
TTL for programming    
INTRABUS voltage driven      
MODBUS master RS-485   
MODBUS slave RS-485    
CANBUS CAN
USB   
Other features
real time clock   
alarm buzzer      
  
Notes
None.
  
Available options
None.

I/O configuration

The picture shows an example of ready for use configuration for dual-circuit air to water chillers/heat pumps with 2 compressors for each circuit , a bipolar stepper electronic expansion valves driver for each circuit (EVDRIVE03), modulating fans and single condensation; it is possible to customize the I/O configuration.

c-pro 3 micro CHILEVDRIVE03 circ. 1EVDRIVE03 circ. 2
Analog inputs
AI1circuit 1 condensation pressure  
AI2circuit 1 discharge temperature  
AI1plant circuit return temperature  
AI2plant circuit supply temperature  
AI3outdoor temperature  
AI4... AI9not usedX  
AI3circuit 1 suction temperature  
AI4circuit 1 evaporation pressure  
AI1circuit 2 condensation pressure  
AI2circuit 2 discharge temperature  
AI3circuit 2 suction temperature  
AI4circuit 2 evaporation pressure  
Digital inputs
DI1circuit 1 high pressure switch  
DI2circuit 1 low pressure switch  
DI3circuit 1 compressor 1 thermal switch  
DI1circuit 2 high pressure switch  
DI2circuit 2 low pressure switch  
DI3circuit 2 compressor 1 thermal switch  
DI1on/off  
DI2plant circuit flow switch  
DI3plant circuit pump thermal switch  
DI4circuit 1 compressor 2 thermal switch  
DI5fan thermal switch (230 VAC)  
DI6summer/winter  
DI7circuit 2 compressor 2 thermal switch  
DI8... DI9not usedX  
Analog outputs
AO1fan  
AO2... AO6not usedX  
Digital outputs (electromechanical relays)
DO1plant circuit pump  
DO2circuit 1 compressor 1  
DO3circuit 1 compressor 2  
DO4plant circuit antifreeze heaterss  
DO5fan enabling  
DO6circuit 1 reversing valve  
DO7circuit 2 compressor 1  
DO8circuit 2 compressor 2  
DO9circuit 2 reversing valve  
DO1circuit 1 pump down solenoid valve  
DO1circuit 2 pump down solenoid valve  