EVBOX1 Datalogging

EVBOX1 Datalogging

Electrical control panels for single-phase cold rooms
EVBOX1 Datalogging is a range of electrical control panels for single-phase cold rooms with data-logging extension for compliance with the EN12830 standard
Equipped with up to 6 relay outputs, the electrical panels can regulate with great flexibility and energy savings the most varied equipment configurations on the market, including those with management of temperatures as low as -99°C.
The controllers use two relays, rated load 30 A @ 250 VAC, for direct control of high-power compressors and the evaporator fan and they can be adjusted for low and high relative humidity.
Some models have a thermal-magnetic circuit breaker and include a driver for unipolar stepper-type electronic expansion valves. They all have a clock for memorising HACCP alarms and a data-logging extension on an SD card with built-in battery for data recording, even in the event of a power failure.
The user interface consists of a large custom display with decimal point and function icons, with six buttons. It guarantees IP65 frontal protection. The controllers are designed to be wall-mounted, with fixing screws and plugs.
Technical sheet
Generate PDF

Advantages & Main Features

Data-logging extension on SD card for compliance with the EN12830 standard.
Variety of models for different typologies of cold rooms.
30 res. A @ 250 VAC electromechanical relay.
Models with a driver for unipolar stepper-type electronic expansion valves.
Models with thermal magnetic circuit breaker.
MODBUS RS-485 communication port.
Adaptive defrost management and energy saving strategies.
Real time clock.
Big size display.
IP65 protection.

Technical Features

Electrical control panels for single-phase cold rooms

EVB1214N9XLCEVB1216N9XLCEVB1216N9MLCEVB1256N9MLC
Power supply
115... 230 VAC
Analog inputs
room probe (PTC/NTC/Pt 1000)
evaporator probe (PTC/NTC/Pt 1000)
auxiliary probe (PTC/NTC/Pt 1000) (1)
auxiliary probe 2 (NTC/Pt 1000)
auxiliary probe 3 (NTC/Pt 1000)
suction pressure probe (4-20 mA)   
evaporating temperature probe (PTC/NTC/Pt 1000)   
Digital inputs (for NA/NC contact)
door switch
multipurpose
multipurpose 2
Digital outputs (electromechanical relays; res. A @ 250 VAC)
compressor30 A30 A30 A30 A
defrost16 A16 A16 A16 A
evaporator fan30 A30 A30 A30 A
room light 16 A16 A16 A
load 4 (default room light) (2)8 A   
load 5 (default condenser fan) (3) 8 A8 A8 A
load 6 (default alarm) (3) 8 A8 A8 A
Communication ports
MODBUS RS-485 for other EVCO products
Other features
real time clock
alarm buzzer
data-logging extension on SD card for compliance with the EN12830 standard
integrated unipolar stepper electronic expansion valves driver   
low or high relative humidity percentage operation
condenser overheat alarm system
adaptive defrost management
"multideck" function
“HACCP” function
“energy saving” function
“quick cooling” function
unipolar thermal magnetic circuit breaker + neutral (230 VAC, In 16 A, Icn 4.500 A)  
  
Notes
(1)configurable for condenser temperature probe, critical temperature probe, evaporator 2 temperature probe or CPT probe
(2)configurable for room light, demisting heaters, auxiliary, alarm, door heaters, heaters for neutral zone operation, condenser fan, compressor 2, defrost 2, evaporator fan 2, pump down valve, on/stand-by or man in cabinet
(3)configurable for demisting heaters, auxiliary, alarm, door heaters, heaters for neutral zone operation, condenser fan, compressor 2, defrost 2, evaporator fan 2, pump down valve, on/stand-by or man in cabinet.
  
Available options
None.