EVDRIVE

EVDRIVE

Driver for bipolar stepper electronic expansion valves
EVDRIVE is a range of drivers for the management of stepper electronic expansion valves.
Available with integrated user interface or in blind version with the possibility of a remote user interface (EPJgraph).
The user interface consists of a LCD graphic display and six keys.
The drivers can manage both generic electronic expansion valves and the more common stepper valves on the market; they can also be used as a simple analog positioner and can work both on a stand alone basis or managed by a controller, guaranteeing an increase in the efficiency of the refrigerating circuit.
The variety of available communication ports (RS-485 and CAN) and supported communication protocols promotes the integration of the drivers in control solutions.
Installation is on DIN rail, into a control panel.
Technical sheet
Generate PDF

Advantages & Main Features

Compatibility with the most diffused stepper electronic expansion valves on the market.
Variety of communication ports (RS-485 and CAN) and supported communication protocols, to promote the integration of the drivers in control solutions.
Increase in the efficiency of the refrigerating circuit.
Standard size 4 DIN modules.
Models with LCD graphic display.
Models with integrated user interface or in blind version.

Technical Features

Driver for bipolar stepper electronic expansion valves

EVDRIVE03EVDRIVE04EVDRIVE06
EPD4BX3EPD4BC3EPD4BF3EPD4DF3EPD4BX4EPD4BC4EPD4BF4EPD4DF4EPD4BX6EPD4BC6EPD4BF6EPD4DF6
Version
blind   
built-in LCD (128 x 64 pixel single colour LCD graphic display)         
Power supply
24 VAC/DC not isolated
Analog inputs
analog input 1 (NTC/Pt 1000/0-20 mA/4-20 mA)        
analog input 1 (NTC/Pt 1000/0-20 mA/4-20 mA/0-5 V ratiometric) (1)    
analog input 2 (NTC/Pt 1000/0-20 mA/4-20 mA/0-5 V ratiometric)
eaporation temperature probe (NTC/Pt 1000)
evaporation pressure probe (0-20 mA/4-20 mA/0-5 V ratiometric/0-10 V)
Digital inputs (for NA/NC contact)
digital input 1 (2)
digital input 2 (2)
high voltage digital input   
Digital outputs (electromechanical relays; res. A @ 250 VAC)
load (default not used) (3)5 A5 A5 A5 A5 A5 A5 A5 A5 A5 A5 A5 A
Communication ports
MODBUS TTL, for Parameters Manager set-up software system and for other EVCO products        
USB    
MODBUS slave RS-485      
CANBUS CAN   
  
Notes
(1)configurable for evaporation temperature backup probe or evaporation pressure backup probe
(2)configurable for operation enabling, parameter set change, valve resynchronization command or backup module status
(3)configurable for alarm, solenoid valve or valve resynchronization.
  
Available options
None.
Per maggiori informazioni su questa gamma consulta la versione desktop del sito.